New Electrical work

PAR Electrical Services - Details below.
More photographs to follow.






SPEGETTI JUNCTION BEING REMOVED AND RELPLACED WITH NEW










MORE NEW PHOTOGRAPHS OF ADDED INSTALLATION TO FOLLOW.





 PAR Electrical Services

NAPIT Registered Contractor
20 Barrington Road
Sutton. SM3 9PP

Form 1
ELECTRICAL INSTALLATION CERTIFICATE (notes 1 & 2)
(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS – BS7671 [17th Edition IEE WIRING REGULATIONS])

DETAILS OF CLIENT (note 1)  Mr B. S. De Souza    Reference: PR29012014
INSTALLATION ADDRESS:  5 Parklands Way
                                              Worchester Park
                                              Surrey KT4 7HT    
DESCRIPTION AND EXTENT OF THE INSTALLATION
Description of installation: Domestic.
Extent of installation covered by this Certificate: New CCU, light and ring circuits in New Kitchen + New Kitchen Extension   
FOR DESIGN

 being the  responsible for the design of the electrical installation (as indicated by  signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the design hereby CERTIFY that the design work for which  have been responsible is to the best of  knowledge and belief in accordance with BS7671: 2008 except for the departures, if any, detailed as follows:

Details of departures from BS7671: 2008
N/A

The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.
For the DESIGN of the installation:    ** (Where there is mutual responsibility for the design)



Signature: ………………………………………..  Date:                                         Name:                     Designer No.1

Signature: ………………………………………..  Date:                              Name:          Designer No. 2**

FOR CONSTRUCTION

I being the person responsible for the construction of the electrical installation (as indicated by my signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that the construction work for which I have been responsible is to the best of my knowledge and belief in accordance with BS7671: 2008 except for the departures, if any, detailed as follows:

Details of departures from BS7671: 17th Edition 2008
N/A

The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.
For the CONSTRUCTION of the installation:    ** (Where there is mutual responsibility for the construction)



Signature: ………………………………………..  Date:                                                     Name:                   Constructor No.1

Signature: ………………………………………..  Date:                                          Name:        Constructor No. 2**



FOR INSPECTION & TESTING
I being the person responsible for the inspection & testing of the electrical installation (as indicated by my signature below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection & testing hereby CERTIFY that the work for which I have been responsible is to the best of my knowledge and belief in accordance with BS7671: 2008 except for the departures, if any, detailed as follows:

Details of departures from BS7671: 17th Edition 2008
None     


The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.
For the INSPECTION & TEST of the installation:

Signature:                                                        Date:  29th January 2014           Name: P.A.Redman  Inspector
NEXT INSPECTION
It is recommended that this installation is further inspected and tested after an interval of not more than 5  (notes 4 and 7)
PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION (note 3)
Designer (No. 1)    Name: N/A
    Designer (No. 2)    Name:      
For and on behalf of      
Telephone:      

Constructor (No. 1)    Name: N/A    Constructor (No. 2)    Name:      
For and on behalf of      
Telephone:      

Inspector    Name: P.A.Redman                                                   Date: 29th January 2014          
For and on behalf of: PAR Electrical Services
Telephone: 0203-673-3529

FOR DESIGN, CONSTRUCTION, INSPECTION &TESTING
I being the person responsible for the design of the electrical installation (as indicated by my signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the design hereby CERTIFY that the design work for which I have been responsible is to the best of my knowledge and belief in accordance with BS7671: 2008 except for the departures, if any, detailed as follows:


Details of departures from BS7671: 17th Edition 2008: Amendment 1
N/A

The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.


Name:
Signature: ………………………………………..
For and on behalf of: …………………………………….
Telephone: …………………………………………………..   
Position:

Date:



SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS. Enter details, as appropriate
Earthing arrangements
TN-S    Number and Type of Live Conductors    Nature of Supply Parameters    Supply
Protective Device Characteristics

   
1 phase supply

If other          Nominal voltage, U/Uo (1)  V
Nominal frequency, f (1) 50 Hz
Prospective fault current, Ipf (2) 0.76A (note 4)
External loop impedance, , Ze (2) 0.33Ω
(Note: (1) by enquiry, (2) by enquiry or by measurement)   
                  Type: BS1361
Nominal current
   rating  60A
Alternative source of supply  (to be detailed on attached schedules)             
PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE Tick boxes and enter details, as appropriate
Means of Earthing

Suppliers facility

Installation of earth electrode     Maximum Demand

Maximum demand (load) 63 Amps per phase

     Details of Installation Earth Electrode (where applicable)
     Type
(e.g. rod(s), tape etc)
         Location

         Electrode resistance to earth

      
Main Protective Conductors
Earthing conductor:
Main equipotential bonding conductors:    Material  csa 16mm2
Material  csa 16mm2    Connection verified
Connection verified
To incoming water service X
To lightning protection     To incoming gas service     To incoming oil service     To structural steel
     To other incoming service(s)  (state details)      
Main Switch or Circuit-breaker
Type: British General.  No. of Poles: 2
Location: Cupboard in T.V room    Current rating 63 A                              Voltage rating 230 V
Fuse rating or setting 100 A
Rated residual operating current In =  30mA, and operating time of 0.4A (at In) (applicable only where an RCD is suitable and is used as main circuit breaker)
COMMENTS ON EXISTING INSTALLATION: (In the case of an alteration see Section 743)
Although the test values for the existing circuitry were within the requirements of BS76771: 2008. Amendment 1, the actual condition of the cables where and when installed in the fabric of the building could not be verified.
SCHEDULE(S) (note 2)
The attached schedules are part of this document and this Report is valid only when they are attached to it.
1 Schedule(s) of Inspections and 1 Schedule(s) of Test Results are attached.
(Enter quantities of schedules attached).

GUIDANCE FOR RECIPIENTS

This safety Certificate has been issued to confirm that the electrical installation work to which it relates has been designed, constructed and inspected and tested in accordance with British Standard 7671 (The IEE Wiring Regulations).

You should have received an original Certificate and the contractor should have retained a duplicate Certificate. If you were the person ordering the work, but not the user of the installation, you should pass this Certificate, or a full copy of it including the schedules, immediately to the user.

The "original" Certificate should be retained in a safe place and be shown to any person inspecting or undertaking further work on the electrical installation in the future. If you later vacate the property, this Certificate will demonstrate to the new owner that the electrical installation complied with the requirements of British Standard 7671 at the time the Certificate was issued. The Construction (Design and Management) Regulations require that for a project covered by those Regulations, a copy of this Certificate, together with schedules is included in the project health and safety documentation.

For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a competent person. The maximum time interval recommended before the next inspection is stated on Page 1 under "Next Inspection".

This Certificate is intended to be issued only for a new electrical installation or for new work associated with an alteration or addition to an existing installation. It should not have been issued for the inspection of an existing electrical installation. A "Periodic Inspection Report" should be issued for such a periodic inspection.








Methods of protection against electric shock    Prevention of mutual detrimental influence
Both basic and fault protection:        (a)        Proximity of non-electrical services and other influences
N/A

N/A

N/A

N/A
    (i)

(ii)

(iii)

(iv)    SELV

PELV

Double insulation

Reinforced insulation     



N/A

   
(b)


(c)   
Segregation of band  and band   circuits or use of
band  insulation.

Segregation of safety circuits

Segregati
Basic protection:    Identification:
    ((i)    Insulation of live parts     LIM
      (a)    Presence of diagrams, instructions, circuit charts and
          similar information.
    (ii)    Barriers or enclosures    Pass    (b)        Presence of danger notices and other warning notices
    (iii)    Obstacles         (c)    Labelling of protective devices, switches and terminals
N/A    (iv)    Placing out of reach        (d)      Identification of conductors

Fault Protection:           

⦁    Automatic disconnection of Supply                                                          
                                                                                              Cables and Conductors
             Presence of earthing conductor

            Presence of circuit protective conductors
              Selection of conductors for current carrying capacity and voltage drop                                                

          Erection methods  




N/A


N/A


N/A




(ii)

N/A

(iii)

N/A

(iv)

N/A


N/A



Pass



     Presence of protective bonding conductors

Presence of supplementary bonding conductors.

Presence of earthing arrangements for combined
protective and functional purposes.

Presence of adequate arrangements for alternative source(s), where applicable

FELV

Choice and setting of protective and monitoring devices (for fault and/or over-current protection)

⦁    Non-Conducting location:
                                                                                              
Absence of protective conductor  

Earth-Free local equipotential bonding:                       

Presence of earth-free local equipotential bonding

Electrical Separation:

Provided for one item of current carrying
Equipment

Provided for more than one item of current
using equipment

Additional protection:
Presence of residual current devices(s).

Presence of supplementary bonding conductors.

Pass: Indicates an inspection has been carried out an the result is satisfactory

N/A: indicates that the inspection is not applicable to a particular item          Pass

 
Pass
                          
General:


N/A

N/A


     Routing of cables in prescribed zones

Cables incorporating earthed armour or sheath, or run
within an earthed wiring system, or otherwise adequate
protected against nails, screws and the like.

Additional protection provided by 30mA RCD for cables in
   concealed  walls (where required in premises not under
the provision of a skilled (or instructed person).

Connection of conductors.

Presence of fire barriers, suitable seals and protection
against thermal effects 

 Presence and correct location of appropriate devices for isolation
and switching.
Adequacy of access to switchgear and other equipment

Particular protective measures for special in installations and
locations 
                                  
Connection of single-pole devices for protection or switching in
line conductors only

Correct connection of accessories and equipment.

Presence of undervoltage protective devices
 S
Selection of equipment and protective measures appropriate to
external influences.

Selection of appropriate functional switching devices.


Fail: indicates an inspection has been carried
out and the result is not satisfactory (applicable
for a periodic inspection only)

LIM: indicates that, exceptionally, a limitation agreed
With the person ordering the work prevented the
Inspection being carried out (applicable for a
Periodic inspection only)

DB reference no 1
Location: Cupboard in T.V Room
Zs at DB () 0.33Ω
Ipf at DB (kA):  0.76
Correct supply polarity confirmed:√
Phase sequence confirmed (where appropriate)  √    Details of circuits and/or installed equipment vulnerable to damage when testing:
Smoke and carbon monoxide detectors dimmer switches ...........................................
.......................................................................................................................................
.......................................................................................................................................
........................................................................................................................................    Details of test instruments used (state serial and/or asset numbers): 8946027 Fluke Multi-meter
Continuity:                       
Insulation resistance:
Earth fault loop impedance:
RCD and Earth electrode resistance:
Tested by: PAR Electrical Services
Name (Capitals): P.A.Redman
Signature                                                              Date: 12th January 2014               Test results
     Ring final circuit continuity (Ω)    Continuity
(Ω)
(R1 + R2)
 or R2     Insulation Resistance (MΩ)     Polarity     Zs
(Ω)    RCD    Remarks
 (continue on a separate sheet if necessary)
Circuit details                         (ms)       
    Overcurrent device    Conductor details                                
Circuit number    
Circuit Description

CCU     type     rating (A)     breaking capacity (kA)     Reference Method     Live (mm2)     cpc (mm2)     r1 (line)     rn (neutral)     r2 (cpc)     (R1 + R2) *     R2     Live-Live     Live-E             @ In    @ 5In    Test button  functionality   
    RCD 1                                                                           
1    Supply to 3rd CCU    B    40    6    C    6.0    2.5    /    /    /    0.12    /    >500    >500    √    0.46    25    10    Good   
2    Radial: 1st Kitchen Hob    B    32    6    C    4.0    2.5    /    /    /    0.16    /    >500    >500    √    0.53    23    12    Good   
3    Ring: New Kitchen    B    32    6    C    2.5    1.5    0.23    0.23    0.38    0.11    /    >500    >500    √    0.46    25    9.7    Good   
4    Ring: Kitchen Extension    B    32    6    C    1.5    1.0    0.18    0.18    0.31    0.12    /    >500    >500    √    0.48    23    12    Good   
5    Lights: Kitchen & Lounge    B    6    6    C    1.5    1.0    /    /    /    0.55    /    >500    >500    √    0.89    26    12    Good   
    RCD 2                                                                           
6    Ring: Kitchen Extension    B    32    6    C    2.5    1.5    0.43    0.43    0.72    0.34    /    >500    >500    √    0.68    36    24    Good   
7    Ring: Lounge + Upstairs    B    32    6    C    2.5    1.5    0.39    0.39    0.65    0.26    /    >500    >500    √    0.64    36    22    Good   
8    Radial: Central Heating    B    16    6    C    2.5    1.5    /    /    /    0.31    /    >500    >500    √    0.69    38    21    Good   
9    Radial: Microwave 2    B    16    6    C    4.0    2.5    /    /    /    0.23    /    >500    >500    √    0.57    38    22    Good   
10    Lights: Kitchen Extension    B    6    6    C    1.5    1.0    /    /    /    0.51    /    >500    >500    √    0.79    39    21    Good   
Generic Schedule of Results
      
 Details of test instruments used (state serial and/or asset numbers): 8946027 Fluke Multi-meter
Continuity:                       
Insulation resistance:
Earth fault loop impedance:
RCD and Earth electrode resistance:
Tested by: PAR Electrical Services
Name (Capitals): P.A.Redman
Signature:    Test results
     Ring final circuit continuity (Ω)    Continuity
(Ω)
(R1 + R2)
 or R2     Insulation Resistance (MΩ)     Polarity     Zs
(Ω)    RCD    Remarks
 (continue on a separate sheet if necessary)
Circuit details                         (ms)       
    Overcurrent device    Conductor details                                
Circuit number    
    type     rating (A)     breaking capacity (kA)     Reference Method     Live (mm2)     cpc (mm2)     r1 (line)     rn (neutral)     r2 (cpc)     (R1 + R2) *     R2     Live-Live     Live-E             @ In    @ 5In    Test button  functionality   
    RCD 1                                                                           
1    Supply to 3rd CCU    B    40    6    C    6.0    2.5    /    /    /    0.12    /    >500    >500    √    0.46    25    10    Good   
2    Radial: 1st Kitchen Hob    B    32    6    C    4.0    2.5    /    /    /    0.16    /    >500    >500    √    0.53    23    12    Good   
3    Ring: New Kitchen    B    32    6    C    2.5    1.5    0.23    0.23            /    >500    >500    √    0.46    25    9.7    Good   

DB reference no 2
Location: Cupboard in New Kitchen Extension
Zs at DB () 0.33Ω
Ipf at DB (kA):  0.76
Correct supply polarity confirmed:√
Phase sequence confirmed (where appropriate)  √    Details of circuits and/or installed equipment vulnerable to damage when testing:
Carbon monoxide detector ……………………………………….....................................
.......................................................................................................................................
.......................................................................................................................................
........................................................................................................................................ 
 Details of test instruments used (state serial and/or asset numbers): 8946027 Fluke Multi-meter
Continuity:                       
Insulation resistance:
Earth fault loop impedance:
RCD and Earth electrode resistance:
Tested by: PAR Electrical Services
Name (Capitals): P.A.Redman
Signature                                                              Date: 12th January 2014               Test results
     Ring final circuit continuity (Ω)    Continuity
(Ω)
(R1 + R2)
 or R2     Insulation Resistance (MΩ)     Polarity     Zs
(Ω)    RCD    Remarks
 (continue on a separate sheet if necessary)
Circuit details                         (ms)       
    Overcurrent device    Conductor details                                
Circuit number    
Circuit Description

CCU 2    type     rating (A)     breaking capacity (kA)     Reference Method     Live (mm2)     cpc (mm2)     r1 (line)     rn (neutral)     r2 (cpc)     (R1 + R2) *     R2     Live-Live     Live-E             @ In    @ 5In    Test button  functionality   
1    Radial: 1st Kitchen Hob    B    32    6    C    4.0    2.5    /    /    /    0.24    /    >500    >500    √    0.58    18    10    Good   
2    Smoke detector    B    6    6    C    1.5    1.0    /    /    /    0.12    /    >500    >500    √    0.48    18    10    Good   



















DB reference no 3
Location: Cupboard in New Kitchen Extension (MK)
Zs at DB () 0.39Ω
Ipf at DB (kA):  0.82
Correct supply polarity confirmed:√
Phase sequence confirmed (where appropriate)  √    Details of circuits and/or installed equipment vulnerable to damage when testing: dimmer switches and electronic controls …………………............................................................................................................
.......................................................................................................................................
.......................................................................................................................................
........................................................................................................................................    Details of test instruments used (state serial and/or asset numbers): 8946027 Fluke Multi-meter
Continuity:                       
Insulation resistance:
Earth fault loop impedance:
RCD and Earth electrode resistance:
Tested by: PAR Electrical Services
Name (Capitals): P.A.Redman
Signature                                                              Date: 12th January 2014               Test results
     Ring final circuit continuity (Ω)    Continuity
(Ω)
(R1 + R2)
 or R2     Insulation Resistance (MΩ)     Polarity     Zs
(Ω)    RCD    Remarks
 (continue on a separate sheet if necessary)
Circuit details                         (ms)       
    Overcurrent device    Conductor details                                
Circuit number    
Circuit Description

CCU 2    type     rating (A)     breaking capacity (kA)     Reference Method     Live (mm2)     cpc (mm2)     r1 (line)     rn (neutral)     r2 (cpc)     (R1 + R2) *     R2     Live-Live     Live-E             @ In    @ 5In    Test button  functionality   
1    Spare                                                                           
2    Ring: Music Room    B    32    6    C    2.5    1.5    0.17    0.17    0.31    0.13    /    >500    >500    √    0.58    18    10    Good   
3    Lights Music Room    B    6     6    C    1.5    1.0    /    /    /    0.38    /    >500    >500    √    0.78    18    10    Good   
4    Radial Oven 1    B    16    6    C    4.0    2.5    /    /    /    0.21    /    >500    >500    √    0.58    18    10    Good   
5    Radial: Oven 2    B    16    6    C    4.0    2.5    /    /    /    0.24    /    >500    >500    √    0.59    18    10    Good   

=======================